top of page

Power Drop
PC-PD

Modular Wiring Component

Application

The Power Drop Module is generally used as a transition from the Plug-N-Go wiring system back to conventional wiring methods. Power Drop Modules may also serve as an interface between the Plug-N-Go system and lighting
fixtures, electrical receptacles or other utilization equipment.

Features

  • Easily installed

  • Full 20 amp rating

  • Single, dual and three circuit models

  • #12 AWG copper conductors standard

  • #10 AWG copper conductors optional

  • 600V, 90º C insulation

  • Dead front construction for safety

  • Connectors are color coded for easy voltage identification

  • Keyed components assure proper connection, function and safety

  • Positive locking clips prevent accidental disconnection

  • Approved for installation in air handling spaces other than ducts and plenums

  • UL listed

Downloads

Additional Information

  • Power Drop Modules consist of a metallic enclosure providing an input connector and an output connector. A flexible armor cable drop is also provided with 8" pigtail leads for easy termination. Power Drop Modules are factory prewired and rated at 20 amps. All models include an internal wiring schematic on the enclosure's cover plate. Power Drop Module connectors provide recessed electrical terminals that result in a dead front design for added safety. All connectors are color coded for easy voltage identification and are keyed to allow mating connections only with components of the same voltage. Secure connections are assured by locking clips on the component rear cup assemblies which prevent accidental disconnection. Cable length is based on project requirements.

  • The principal function of the Power Drop Module is as an interface between components of the Plug-N-Go system and fixtures, receptacles or other utilization equipment, as well as to transition back to conventional wiring methods.

    NOTE: Power Drop Modules are manufactured using type MC cable with #12 AWG copper conductors and 90°C insulation and should be supported in accordance with National Electrical Code requirements.

  • Connector Color → Voltage

    Gray → 277/480 and 480VAC

    Brown →120/208, 208 and 240VAC

    Purple → Dual Neutral 120/208VAC

    Khaki → Dual Neutral 277/480VAC

    Green → Isolated Ground 120/208VAC